NEC Table 310.16 copper conductor values.
Most solar DC runs use 90°C rated USE-2 / PV wire; NM-B indoor cable is limited to the 60°C column even with 90°C insulation.
Temperature of the air/conduit around the wire. Tables assume 30°C.
More bundled wires heat each other — the safe current drops.
Enter your circuit's continuous current to check the wire passes or fails. For a PV string use array Isc × 1.25.
0 base ampacity from table (A)
0 adjusted ampacity (A)
0 max breaker / fuse (A)

Adjusted ampacity = base table value × temperature factor × bundling factor. The breaker must not exceed the adjusted ampacity. Always verify against your local electrical code.

How the wire ampacity calculator works The base ampacity from NEC Table 310.16 is reduced by the ambient temperature and bundling factors, then used to select the maximum breaker size. What you enter Wire size AWG / kcmil Insulation rating 60 / 75 / 90°C Base ampacity (A) NEC Table 310.16 Temp. factor ambient above 30°C Bundling factor wires in one conduit Adjusted ampacity (A) base × both factors Max breaker = next standard ≤ adjusted
How the calculator turns your wire size and conditions into a safe current rating and breaker size.

Ampacity vs ambient temperature

This curve updates with your inputs. It shows how the adjusted ampacity of your selected wire falls as ambient temperature rises at your chosen insulation rating and bundling — the dashed line marks where standard breakers land, so you can see which breaker sizes stay safe.

Adjusted ampacity falls as ambient temperature rises.

The ampacity of a wire is the maximum continuous current it can carry without overheating — and it is the number that decides whether your fuse or breaker actually protects the cable. Get it wrong and a breaker sized too large lets an overloaded wire cook quietly inside the conduit; get it right and every component in the chain is protected.

The rule: base table value × correction factors

NEC Table 310.16 gives the base ampacity for each conductor size and insulation rating, assuming 30°C ambient and three or fewer current-carrying conductors. Your real installation rarely matches those conditions, so the code applies correction factors on top:

Adjusted ampacity = base ampacity × temperature factor × bundling factor

Then the breaker or fuse must be rated at or below that adjusted value. For example, 10 AWG THWN-2 has a base ampacity of 40 A at 90°C; in a 45°C rooftop conduit with 4 bundled conductors that becomes 40 × 0.87 × 0.80 = 27.8 A, so the maximum breaker is 25 A, not the 40 A you might guess from the table alone.

Choosing the insulation column

The column you use is set by the wire's insulation, not its size. USE-2 and PV wire common on rooftops are rated 90°C, as is THHN/THWN-2 in dry locations. NM-B (Romex) is a special case: even though its insulation is rated 90°C, the code limits it to the 60°C column for ampacity. When terminations are rated 75°C, use the 75°C column for the final run — a detail covered by NEC 110.14(C).

Ambient temperature and bundling

Every degree above 30°C reduces what the wire can safely carry — the correction factors come from NEC Table 310.15(B)(1). A conduit on a sun-baked roof in Amman or Arizona can sit at 45-50°C in summer, cutting ampacity by a quarter. Bundling adds up fast too: 4-6 conductors in one conduit derate to 80%, 7-9 to 70%, and 10-20 to 50%. The equipment ground doesn't count as a current-carrying conductor, so a typical PV pair plus ground stays in the "no derating" zone.

Picking the breaker

Round the adjusted ampacity down to the next standard breaker size — 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100 A and so on. NEC 240.4(B) allows the next standard size up when the adjusted value falls between sizes and the load fits, which is how many solar installs land on a 30 A breaker for a 26 A adjusted value. On the load side, keep continuous solar circuits at or under 80% of the breaker rating.

Field note from a Jordanian installer

On the Ma'an projects the rooftop conduit runs were the real test: 40°C+ summer ambient, dark conduits on bare roofs, and string home-runs bundled with monitoring cables. The 10 AWG THHN runs that looked fine on paper needed re-checking against the derated value — several needed upsizing to 8 AWG to keep the 30 A breaker legit. The lesson: always calculate with worst-case summer temperature, not the comfortable spring day you install on.

Work it with the other wiring tools

Ampacity is only half the story — the other half is voltage drop. Once this calculator confirms the wire is safe, check the run length with the voltage drop calculator, and if you're starting from a load, the cable size calculator does both checks in one. For the breaker side, the fuse & breaker sizing calculator applies the 1.25 continuous-load rule, and the watts to amps calculator turns your power figure into the current this tool needs.

Related guides

For a full walk-through of conductor sizing on the DC side, see the guide on what size cable you need for solar panels and inverters, and for choosing overcurrent protection on the PV array side, read the solar inverter buying guide protection sections.

Frequently asked questions

What is wire ampacity?

It is the maximum continuous current a conductor can carry without exceeding its insulation temperature. It depends on size, insulation rating, ambient temperature, and bundling — NEC Table 310.16 is the standard reference.

Which insulation rating should I use for solar wire?

Most PV wire and USE-2 is 90°C; THHN/THWN-2 is 90°C dry and 75°C wet; NM-B indoor cable is limited to the 60°C column. Use the rating printed on the cable sheath, limited by termination ratings.

Why does ambient temperature reduce ampacity?

Tables assume 30°C. Hotter surroundings slow heat shedding, so the code applies correction factors — a 50°C rooftop run can cut ampacity by up to 25% versus the table value.

How does bundling wires together reduce ampacity?

Bundled conductors heat each other. NEC derating: 1-3 conductors = 100%, 4-6 = 80%, 7-9 = 70%, 10-20 = 50% of base ampacity. The equipment ground doesn't count.

How do I pick the breaker size from the ampacity?

Choose the next standard breaker size at or below the adjusted ampacity. NEC 240.4(B) allows the next size up when the adjusted value falls between sizes and the continuous load fits.

Does this calculator work for both DC and AC wiring?

Yes — ampacity is a property of the conductor. Use array Isc × 1.25 for PV string currents on the DC side and the continuous load current on AC circuits; the table and factors are the same.