Cross-sectional area of your conductor. Common sizes: 2.5, 4, 6, 10, 16, 25 mm².
Distance one way from source to load. The round trip is handled automatically.
Current flowing through the cable in amps. If you know watts: A = W ÷ V.
Your system's nominal voltage — used to express the drop as a percentage.
Copper is standard. Aluminium has higher resistance so more drop for the same size.
0 V voltage drop
0% of system voltage

Round-trip distance (out and back) is already accounted for. Copper resistivity 0.0175, aluminium 0.0282 Ω·mm²/m.

How the voltage drop calculator works Cable length, current, and cross-sectional area combine to give the voltage drop in volts, which divided by system voltage gives the percentage drop. What you enter Length metres Current amps Cable size mm² Voltage drop (V) 2 × L × I × ρ ÷ area Divide by system voltage drop ÷ V × 100 Voltage drop as %
How the calculator turns your cable details into voltage drop.

How voltage drop grows with cable length

This curve updates with your inputs above. It shows how the voltage drop percentage rises as the cable run gets longer — the further the power has to travel, the more voltage is lost along the way.

Voltage drop percentage rises as cable length increases.

Voltage drop is the quiet performance-killer of solar and DC wiring. Every cable has some resistance, and pushing current through that resistance loses a bit of voltage along the way — energy that turns into heat instead of reaching your batteries, inverter, or loads. Our cable size calculator works the other direction (it picks a cable size for an allowable drop); this tool is for when you already have a cable in mind and want to know the actual drop it will produce.

The formula

For a DC or single-phase run, voltage drop is:

Voltage drop (V) = 2 × L × I × ρ ÷ A

Where L is the one-way cable length in meters, I is the current in amps, ρ (rho) is the conductor resistivity (0.0175 Ω·mm²/m for copper, 0.0282 for aluminium), and A is the cable's cross-sectional area in mm². The × 2 accounts for the current traveling out to the load and back. To express it as a percentage, divide by the system voltage and multiply by 100.

A worked example

Take a 6 mm² copper cable, 10 m one-way, carrying 20 A on a 48 V system:

That's within the common 3% guideline, so this cable is fine for this run. If you dropped to a 4 mm² cable, the drop would rise to about 3.5% — over the limit, and a sign you'd want the thicker conductor.

What counts as acceptable?

The widely used rule of thumb is 3% or less for main power cables, and 5% maximum for the total across all runs. Lower is always better — every bit of dropped voltage is wasted energy. On low-voltage systems (12 V and 24 V) voltage drop is especially punishing, because even a small voltage loss is a big percentage of the system voltage. This is one of the strongest arguments for wiring larger systems at 48 V.

Three ways to reduce voltage drop

Related tools

If the drop you get here is too high, use the cable size calculator to find the correct size for your target drop. To work out the current from your load, the daily load calculator and panel calculator can help you understand your system's power and current draw.

Frequently asked questions

How do I calculate voltage drop in a cable?

Voltage drop = 2 × one-way length × current × resistivity ÷ cross-sectional area. The ×2 covers the out-and-back path. For copper, resistivity is about 0.0175 Ω·mm²/m. Divide by system voltage for the percentage. This calculator does it all automatically.

What is an acceptable voltage drop for solar cables?

Keep it at or below 3% for main cables, and under 5% total. Lower is better since dropped voltage is wasted energy. Low-voltage 12V/24V systems need extra care because a small drop is a big percentage.

Why does voltage drop matter?

It wastes energy as heat, reduces voltage delivered to equipment, and can cause devices to underperform. Excessive drop on undersized cable also causes overheating — a safety hazard.

How can I reduce voltage drop?

Use a thicker cable, shorten the run, or raise the system voltage. Thicker cable is the usual fix; higher voltage is very effective because it lowers the current for the same power.